  • Planning application 2660530 at Co. Clare: Ten-year permission for development.
  • The applicant is Electricity Supply Board (ESB. The agent is Philip Glennon.
  • It was received by Clare County Council on 17 Aug 2026.
  • Status: Decision date passed (11 Oct 2026); check the council file.
  • The decision date (11 Oct 2026) has passed with no decision recorded yet. Check the council file before treating this as live.

Source: the Clare County Council planning register, checked 12 Oct 2026. Open the council's file

Planning applications in Co. Clare

What and where

Ten-year permission for development

for a ten-year permission for development on lands comprising the former coal storage area, within the existing Moneypoint Generating Station landholding in the townland of Carrowdotia South, and ESB owned lands within the maritime area, County Clare. The proposed development will comprise the construction/installation of a Long Duration Energy Storage (LDES) facility and associated plant and equipment, within a fenced compound, comprising the following main components: • LDES Area- Up to 564 No (c. 6.8m L x 2.4m W x 3.1m H) LDES enclosures split across 47 No linear bays, within 12 No blocks. Each linear bay contains 2 rows of 6 LDES enclosures. Each bay will be on a concrete plinth measuring c. 57.1m L x 6.5m W x 0.3m H;- 47 No Medium Voltage (MV) Battery Energy Storage System (BESS) Inverter Skids/ Twin Inverter Skids (c. 12.8m L x 6m W x 2.4m H) and associated plinths (c. 13.3m L x 6.5m W x 0.3m H), bunds and fire walls;- 10 No Auxiliary Transformers (c. 2.6m L x 2m W x 3m H including foundation / plinth), associated bunds (c. 4m L x 4m W x 0.8m H) and fire walls;- 2 No MV Switchgear Pre-fabricated Buildings (c. 18.85m L x 6m W x 4.6m H);- 5 No Low Voltage Switchgear Containers (c. 8m L x 5m W x 3.61m H);- Noise barrier (c.194m L x 6m H); • Ancillary Equipment- 1 No Power Quality Equipment (c. 5m L x 5m W x 3m H); - 1 No Fire Water Storage Tank (c. 13.4m diameter x 9.8m H) on c. 14.5m diameter x 0.35m H plinth; - 1 No Fire Water Pumphouse (c. 10m L x 6.2m W x 5.4m H);- 4 No 40” Spares Containers (c. 12.2m L x 2.4m W x 2.59m H);- 4 No Back Up Diesel Generator Plinths (c. 7m W x 4.1m L x 0.15m H); - 1 No operational & maintenance Portakabin (c. 9.15m L x 3.05m W x 3.15m H);- 1 No Double Toilet Block (c. 2.4m L x 1.2m W x 2.5m H) with Foul Holding Tank;- 1 No Below ground Fire Water Retention Tank;- Modifications to the existing Settlement Pond; • High Voltage Air Insulated Switchgear (AIS) Compound (c. 3068 m² footprint), bounded by up to 4m H palisade fencing, containing - 1 No Step-Up Transformer (c. 18m L x 8m W x 11m H) and associated bund (c. 23.2m L x 19.7m W) and fire walls (c. 11m H); - Associated electrical equipment including, Current transformers / voltage transformers (CT/VT) Circuit Breakers, Neutral Earth Resistors, Cable Chairs, and Line Earth Disconnects; • 1 No Prefabricated Electrical Control (PEC) /Modular Control and Protection Building (c. 18.85m L x 4.2m W x 4.6m H); • The Proposed LDES development will connect via underground cable into the national grid at the existing Moneypoint substation. • All associated development including site enabling, services and development works, including areas of hardstanding, car parking, internal access, lighting poles (c. 6m high), lightning monopoles (c.30m high), CCTV poles (c.8m high), perimeter fencing (c. 4m high), fire walls (c. 2.9m high), telecommunications, landscaping, drainage, trenching and ducting, temporary construction compounds and all other ancillary works. A Natura Impact Statement has been prepared and will be submitted to the planning authority with this planning application. The application site is located within lands which are categorised as an Upper Tier COMAH site (Moneypoint Generating Station) and therefore falls under the requirements of the Control of Major Accident Hazard (COMAH) Regulations, 2015. The Proposed Development does not require an Industrial Emissions (IE) Licence or an Integrated Pollution Control (IPC) Licence; it is, however, located within a site that already holds an IE Licence. Note: Separate future planning applications will be submitted for nearby proposed development also within the existing Moneypoint Generating Station landholding, in the townlands of Carrowdotia North, Carrowdotia South, and Ballymacrinan, Killimer, Kilrush, County Clare (Eircode V15 R963), consisting of 2 No separate proposed Open Cycle Gas Turbine (OCGT) development, to provide power to the national electricity grids. The OCGT applications will be made separately and directly to An Coimisiún Pleanála pursuant to Section 37A of the Planning and Development Act 2000, as amended (or successor legislation).

Description as published by the council. Its text starts part-way through a sentence.

Location
Co. Clare Map
Planning reference
2660530
Application type
Permission
Council planning fileGet alerts

Numbers and dates

Floor area
3,068 m²
Received
17 Aug 2026
Decision due
11 Oct 2026Date passed; check the council file

Timeline

  1. Application received
  2. Further information requested

Outlook

What happens next

The decision date (11 Oct 2026) has passed with no decision recorded yet. Check the council file before treating this as live.

Work packages named so far

  • Services and drainageNamed in the application description

An outlook from the planning record, not a tender or a confirmed start date.

Documents and evidence

Check the record

  • Council planning fileThe application file 2660530 on eplanning.ie: drawings, reports and the decision.Open the council's file

Reviewed build intelligence

What the documents establish

Government document review

Application received 17 August 2026. The August report defines a proposed design envelope; no planning decision, agreed connection or operational equipment is established.

1 official documents inspected · Checked 2026-09-06 · Official file index

The application describes an approximate 300 MW storage design

August 2026 application; approximate capacity and detailed-design limits retained · Clare 2660530; new LDES proposal, separate from other Moneypoint generation projects

What the evidence says
The August report proposes a battery-storage development of approximately 300 MW within Moneypoint’s former coal-storage area. Its physical envelope allows up to 564 enclosures in 47 linear bays within 12 blocks, 47 MV/inverter skids and 10 auxiliary transformers. It treats the capacity as indicative and the physical parameters as an upper design envelope. No energy capacity in MWh is calculated from the generic discussion of storage duration.

Why it may matter — interpretation
Energy and grid engineers can distinguish the planning envelope from a final electrical or energy-capacity specification.

What is not established
Final MW and MWh ratings, decision, selected supplier, construction and operation are unverified.

Inspect the evidence

Moneypoint LDES: planning and environmental considerations report · p.103
c.300 MW · Issued August 2026 (month only) · PL1; 229101734-MMD-0000-XX-RP-C-001; August 2026; received 17 August 2026. PDF page numbers include 30 front-matter pages. · Checked 2026-09-06

c.300 MW

Lithium-ion is the stated preferred technology, not a selected battery product

August 2026 application; approximate capacity and detailed-design limits retained · Planning-stage technology preference and separate network agreement

What the evidence says
The report selects lithium-ion as its preferred storage technology, while allowing future technology improvements within the assessed physical parameters. It does not identify a battery-cell chemistry variant, enclosure manufacturer or final system model. The proposed HV connection to the existing Moneypoint substation remains subject to EirGrid agreement.

Why it may matter — interpretation
Battery and protection engineers can assess the stated technology basis while keeping product selection and network acceptance open.

What is not established
Cell chemistry, supplier, final controls/protection design and agreed grid connection are unverified.

Inspect the evidence

Moneypoint LDES: planning and environmental considerations report · p.101
preferred technology · Issued August 2026 (month only) · PL1; 229101734-MMD-0000-XX-RP-C-001; August 2026; received 17 August 2026. PDF page numbers include 30 front-matter pages. · Checked 2026-09-06

preferred technology

Moneypoint LDES: planning and environmental considerations report · p.109
EirGrid · Issued August 2026 (month only) · PL1; 229101734-MMD-0000-XX-RP-C-001; August 2026; received 17 August 2026. PDF page numbers include 30 front-matter pages. · Checked 2026-09-06

EirGrid

The transformer-bund design names Entexol systems or approved equivalents

August 2026 application; approximate capacity and detailed-design limits retained · MV-skid and auxiliary-transformer bund-water handling; different details remain separate

What the evidence says
The MV-skid description proposes locally bunded transformers and Entexol SCS001 oil-sensitive dewatering or an approved equivalent. The ten auxiliary transformers additionally describe Entexol SCS002 integrated Class 1 full-retention oil separation or an approved equal. The report leaves the final drainage design dependent on the chosen supplier; these are stated alternatives, not evidence of a placed order.

Why it may matter — interpretation
Drainage and electrical engineers can compare proposed bund-water controls and equivalent systems against the final transformer design.

What is not established
Final supplier, bund calculations, separator sizes, approval and installation are unverified.

Inspect the evidence

Moneypoint LDES: planning and environmental considerations report · p.107
Entexol SCS001 · Issued August 2026 (month only) · PL1; 229101734-MMD-0000-XX-RP-C-001; August 2026; received 17 August 2026. PDF page numbers include 30 front-matter pages. · Checked 2026-09-06

Entexol SCS001

The report gives both five and four LV containers

August 2026 application; approximate capacity and detailed-design limits retained · Component list versus detailed LV section; PDF pages 104 and 107, printed pages 74 and 77

What the evidence says
The development-component list on PDF page 104 states five low-voltage switchgear containers. The later dedicated LV section on PDF page 107 states four prefabricated containers. This is an unresolved count disagreement within the same report; neither number is treated as a final equipment total.

Why it may matter — interpretation
Electrical designers can resolve the inconsistent LV schedule before sizing auxiliary distribution or comparing equipment quantities.

What is not established
The controlling LV count and final drawings are not established.

Inspect the evidence

Moneypoint LDES: planning and environmental considerations report · p.104
5 No · Issued August 2026 (month only) · PL1; 229101734-MMD-0000-XX-RP-C-001; August 2026; received 17 August 2026. PDF page numbers include 30 front-matter pages. · Checked 2026-09-06

5 No

Moneypoint LDES: planning and environmental considerations report · p.107
4 no. · Issued August 2026 (month only) · PL1; 229101734-MMD-0000-XX-RP-C-001; August 2026; received 17 August 2026. PDF page numbers include 30 front-matter pages. · Checked 2026-09-06

4 no.

Firewater supply and incident-water retention are separate systems

August 2026 application; approximate capacity and detailed-design limits retained · Supply tank and separate retention system described in section 3.3.3.1

What the evidence says
The report proposes a northern firewater supply tank of approximately 13.41 m diameter and maximum capacity about 1,378 m³, with the stored volume to be agreed during detailed design. It separately identifies a firewater pumphouse and below-ground retention tank. The stated supply-tank maximum is not assigned to the separate retention system.

Why it may matter — interpretation
Fire-protection and drainage engineers can keep firefighting supply and contaminated-water retention requirements distinct.

What is not established
Agreed firewater volume, pump duties, incident-retention volume, final safety design and installation are unverified.

Inspect the evidence

Moneypoint LDES: planning and environmental considerations report · p.107
firewater supply tank · Issued August 2026 (month only) · PL1; 229101734-MMD-0000-XX-RP-C-001; August 2026; received 17 August 2026. PDF page numbers include 30 front-matter pages. · Checked 2026-09-06

firewater supply tank

Four plinths do not establish four permanently installed generators

August 2026 application; approximate capacity and detailed-design limits retained · Contingency supply and permanent support plinths are different scope items

What the evidence says
The report describes secondary electrical supply and a temporary backup diesel generator as alternatives during outages. It proposes four permanent concrete plinths to accommodate temporary generators if required and if secondary supply is unavailable. It does not establish permanently installed diesel sets or their ratings.

Why it may matter — interpretation
Electrical and civil engineers can distinguish fixed enabling works from conditional backup equipment when reviewing the supply strategy.

What is not established
Final backup arrangement, generator count in use, output, fuel storage and installed equipment are unverified.

Inspect the evidence

Moneypoint LDES: planning and environmental considerations report · p.108
temporary backup · Issued August 2026 (month only) · PL1; 229101734-MMD-0000-XX-RP-C-001; August 2026; received 17 August 2026. PDF page numbers include 30 front-matter pages. · Checked 2026-09-06

temporary backup

A new drainage network would feed the modified settlement pond

August 2026 application; approximate capacity and detailed-design limits retained · LDES surface water and the existing coal-yard settlement pond

What the evidence says
The report says the existing coal-yard drainage is not fit for purpose. It proposes a new underground surface-water network, an oil separator and discharge to the modified southern settlement pond. The pond is existing infrastructure; the description does not establish a wholly new pond or a verified discharge capacity.

Why it may matter — interpretation
Civil engineers and drainage suppliers can identify replacement-network work and the retained pond interface that needs assessment.

What is not established
Pond condition, hydraulic design, separator specification, permitted discharge and completed works are unverified.

Inspect the evidence

Moneypoint LDES: planning and environmental considerations report · p.120
new surface water network · Issued August 2026 (month only) · PL1; 229101734-MMD-0000-XX-RP-C-001; August 2026; received 17 August 2026. PDF page numbers include 30 front-matter pages. · Checked 2026-09-06

new surface water network

The initial enabling works are shared with other repowering projects

August 2026 application; approximate capacity and detailed-design limits retained · Shared repowering enabling stage versus LDES-specific civil and electrical work

What the evidence says
The report describes early civil enabling works across the coal-storage area as common to LDES and the two OCGT developments. Later LDES works include reinforced-concrete foundations, with piling or ground improvement where necessary, and separate LDES/HV electrical fit-out. Shared enabling works are not counted as three independent site-preparation packages.

Why it may matter — interpretation
Civil designers and project teams can separate common infrastructure from the later storage package when comparing scope and sequencing.

What is not established
Ground investigations, final foundation method, contracted work packages and actual start dates are unverified.

Inspect the evidence

Moneypoint LDES: planning and environmental considerations report · p.110
common to all three · Issued August 2026 (month only) · PL1; 229101734-MMD-0000-XX-RP-C-001; August 2026; received 17 August 2026. PDF page numbers include 30 front-matter pages. · Checked 2026-09-06

common to all three
Remaining document questions
  • Which later official decision, approved detail or revision changes these source-specific findings?
  • Has a phase-specific official record established the selected equipment or installed specification?

Selected pages of 1 government-published PDFs were visually inspected. 22 catalogue rows retained. Three PDFs were retrieved; selected pages of the 468-page environmental report support these findings. The cover and CEMP were text-screened only. This is not a review of all environmental chapters, appendices or drawings. Proposals do not establish procurement or installed work.

How we know this

From the Clare County Council planning register, checked 12 Oct 2026. We link to the council's own file so you can check the official record before you act. Facts from the planning documents were read from the documents in that file.

Explore the area

More planning activity near Co. Clare

Get alerts for Co. ClareFree. We email you when new applications appear.

Free email alerts

Get new Clare projects by email

New applications, decisions and site starts in Co. Clare. Only when there is something new.

We send a confirmation link first. Nothing starts until you click it. You can unsubscribe at any time.

Email alerts for this applicationMore alert options